Product Center

Product Display

Home>Product>Fire Alarm Cable>FPLR Fire Alarm Cable

FPLR Fire Alarm Cable

Category::UL Fire Alarm Cable

Views:1064Times

Release Date:2024-01-22

Contact Us

< >

Detailed Introduction

The UL listed FPLR type shielded power limited fire alarm riser cable is suitable to be use in a vertical runs in signaling & fire alarm system. It works in high temperature levels. This cable is constructed with FR-PVC insulation and outer jacket with aluminum and PE tape shielding that meets UL 1666 specications. This cable complies with VW - 1 Flame Test requirements in ANSI/UL 1581.

Tested as per ANSI/UL 1666 for ame propagation height of electrical and optical - Fibre Cables Installed Vertically in Shafts.

· Certificate: UL Listed

· Standard: UL 1424 / NEC Article 760

· Temperature: -20°C to 105°C

· Voltage: 300 V

· Compliance: FPLR/CMR/CL3R, flame test UL 1666   /    FPL/CM/CMG/CL3, flame test UL 1685

· Application: Riser fire alarm wiring   /    General purpose fire alarm wiring

Date Sheet

Main parts and material

Conductor

Multiconductor, solid or stranded bare copper

Insulation (Dielectric)

Flame retardant PVC, color red & black (2C)

Shield

Aluminum mylar tape

Drain wire (Earth wire)

Tinned copper, 7 x stranded 0.2mm dia.

Rip cord

150D Nylon, white

Jacket

Flame retardant PVC, color red

 

Available size (Solid conductor)

Size

Conductor

Max DCR

Insulation THK

Jacket THK

Nom. Cable OD

Ref. No.

Type

Nominal dia (mm)

Section (mm2)

20°C, Ω/km

mm

mm

mm

22 AWG x 4C

Solid

0.64 x 4C

0.32

59.1

0.26

0.6

3.8

C0301

18 AWG x 2C

Solid

1.02 x 2C

0.82

21.4

0.26

0.6

5.2

C0302

18 AWG x 4C

Solid

1.02 x 4C

0.82

21.4

0.26

0.7

6.2

C0303

16 AWG x 2C

Solid

1.29 x 2C

1.31

13.5

0.26

0.7

5.8

C0304

16 AWG x 4C

Solid

1.29 x 4C

1.31

13.5

0.26

0.7

6.8

C0305

14 AWG x 2C

Solid

1.63 x 2C

2.08

8.45

0.26

0.7

6.9

C0306

12 AWG x 2C

Solid

2.05 x 2C

3.31

5.31

0.26

0.7

8

C0307

 

Available size (Stranded conductor)

Size

Conductor

Max DCR

Insulation THK

Jacket THK

Nom. Cable OD

Ref. No.

Type

Nominal dia (mm)

Section (mm2)

20°C, Ω/km

mm

mm

mm

22 AWG x 4C

7 stranded

0.73 x 4C

0.32, min

55.4

0.26

0.6

4.6

C0311

18 AWG x 2C

7 stranded

1.16 x 2C

0.81, min

21.9

0.26

0.6

5.4

C0312

18 AWG x 4C

7 stranded

1.16 x 4C

0.81, min

21.9

0.26

0.7

6.5

C0313

16 AWG x 2C

7 stranded

1.46 x 2C

1.28, min

13.7

0.26

0.7

6.7

C0314

16 AWG x 4C

7 stranded