UK Standard Fire Resistant Cable

Category::Fire Alarm Cable

Views:3194Times

Release Date:2020-12-20

Contact Us

< >

Detailed Introduction

PRODUCT DESCRIPTION

◆ Fire Resistant Cables are manufactured with latest technology to ensure consistent quality and reliability.

◆ Conductor: Solid bare copper (IEC/ EN 228, BS 6360, VDE 0295, HD 383)

◆ Insulation: Fire resistant silicon rubber (HD 22.1,BS 7655 EI2), colors: BS7671/HD308-S2/VDE0293-308 (for more than 5 cores white core/black numbered)

◆ Separator: Polyester tape

◆ Drain Wire: 0.80 mm Solid tinned copper

◆ Shield: Aluminium laminated polyester tape

◆ Sheath: HFFR, Red (RAL 3000)or White; EN 50290-2, VDE 0207 HM2, BS 7655 LTS1 /LTS3


KEY APPLICATIONS

◆ Fire detection and fire alarm systems for buildings.

◆ Voice alarm systems.

◆ Emergency voice communication.

◆ Emergency and escape lighting.

◆ Other essential service control circuits for ‘standard’ fire resistance.

Date Sheet

Part N0.

Conductor Spec.

Dia. (+/-5%)mm

Copper W (kg/km)

Cable W. (kg/km)

ECFC039

2×1.00mm²

5.80

23

51

ECFC040

3×1.00mm²

6.00

32

65

ECFC041

4×1.00mm²

6.60

41

81

ECFC042

2×1.50mm²

6.65

33

70

ECFC043

3×1.50mm²

6.75

46

90

ECFC044

4×1.50mm²

7.60

59

110

ECFC045

2×2.50mm²

7.80

50

100

ECFC046

3×2.50mm²

8.25

72

135

ECFC047

4×2.50mm²

9.10

95

165